An FRP ladder cable tray has two pultruded side rails joined by rungs at regular spacing, usually 225–300 mm. It is the standard choice for power and control cables in corrosive plants because it carries heavy loads over long spans, ventilates cables well and sheds water and dust. Select it by cable load, support span, temperature and environment, then confirm the load class from a tested load table.
Of all cable support types, the ladder tray carries the most load for the least material. Its open rungs let air circulate around the cables, which helps current-carrying capacity. Water, dust and process spills drain through instead of pooling. Cables can be tied or cleated to any rung. That combination is why ladder trays are the default for main power and control routes in refineries, chemical plants, power stations, fertiliser complexes and coastal facilities.
In fibre-reinforced plastic (FRP, or GRP), the ladder format adds corrosion resistance, electrical insulation and light weight. This guide covers construction, standard sizes, rung spacing, load classes, cleating and a step-by-step selection method. It draws on how we design and test ladder trays at FGPL, an ADNOC- and EIL-approved FRP cable tray manufacturer.
FGPL makes pultruded FRP ladder, perforated and trough trays with fittings, supports and documents.
01How an FRP ladder tray is built
Side rails
Side rails are pultruded profiles, usually a C-channel or an I-shape with an inward-facing flange to support the rungs. The rail does most of the structural work: it acts as a beam between supports. Rail height and wall thickness set the load capacity and stiffness.
Rungs
Rungs are smaller pultruded profiles, typically rectangular hollow, C-shaped or I-shaped. They carry cable weight across the tray width into the rails. Many manufacturers design rungs to carry a concentrated load of about 90 kg (200 lb) at mid-width, which represents a person stepping on the tray during installation. That is not an invitation to walk on trays, but it shows the robustness expected.
Rung-to-rail joints
Rungs are fixed to rails by mechanical fasteners, bonding, or both. Good joints keep the tray square during handling and do not loosen under vibration. Ask how the joint is made and tested.
Surface
Outdoor trays need a synthetic surface veil and UV inhibitors so the outer layer is resin-rich. Without this, UV exposure erodes the surface resin and leaves exposed fibres (“fibre bloom”).
02Standard sizes of FRP ladder cable trays
| Parameter | FGPL range | Typical use |
|---|---|---|
| Inside width | 150 mm to 1500 mm | 150–300 mm branch runs; 450–900 mm main racks; 1000–1500 mm for very high cable counts |
| Side-rail height | To project requirement; commonly 75–150 mm | 75–100 mm for moderate loads; 150 mm for heavy loads and long spans |
| Rung spacing | Commonly 225–300 mm | 300 mm for large power cables; closer spacing for smaller cables |
| Standard length | 3 m and 6 m | 3 m for congested units and manual handling; 6 m for long racks |
| Resin | Polyester, vinyl ester, epoxy | See resin guidance below |
| Grades | Fire-retardant, UV-stabilised | Specify both for outdoor industrial use |
Choose width from cable fill plus spare capacity, which many project specifications set at 20–30%. Choose side-rail height from the cable depth (load depth) and the structural demand of load and span.
03NEMA load classes and what they mean in kg/m
FRP cable trays are commonly rated using NEMA FG 1 span/load classes. The class code combines the support span in feet with a letter for the working load: A is 50 lb/ft (74 kg/m), B is 75 lb/ft (112 kg/m) and C is 100 lb/ft (149 kg/m). A “20C” tray carries 149 kg/m on a 6.1 m span; a “12B” tray carries 112 kg/m on a 3.66 m span.
NEMA FG 1 tests a single, simply supported tray span and requires a minimum safety factor of 1.5 against failure at the rated load. IEC 61537 instead tests a continuous multi-span arrangement with a splice in the span and uses a 1.7 factor, with deflection limited to span/100 at the safe working load. Some manufacturers publish IEC safe working loads in kg/m for given spans rather than NEMA codes. Either is fine. What matters is that the figure comes from a test.
| Class | Span | Working load | Metric equivalent |
|---|---|---|---|
| 8A | 8 ft | 50 lb/ft | 74 kg/m at 2.44 m |
| 8C | 8 ft | 100 lb/ft | 149 kg/m at 2.44 m |
| 12A | 12 ft | 50 lb/ft | 74 kg/m at 3.66 m |
| 12B | 12 ft | 75 lb/ft | 112 kg/m at 3.66 m |
| 12C | 12 ft | 100 lb/ft | 149 kg/m at 3.66 m |
| 20B | 20 ft | 75 lb/ft | 112 kg/m at 6.10 m |
| 20C | 20 ft | 100 lb/ft | 149 kg/m at 6.10 m |
Shorter spans carry more
Load capacity rises steeply as span shortens, because FRP trays are usually limited by deflection, and deflection grows with the fourth power of span under uniform load. A tray rated for a class at 3.66 m will carry substantially more at 2.4 m. Use the manufacturer’s load table for the actual span rather than scaling by hand.
Check the FRP cable tray range, widths and resin grades, then send your cable schedule for a load check.
04Step-by-step: selecting an FRP ladder tray
-
Total the cable weight per metre for the tray section from the cable manufacturer’s data sheets (kg/m for each cable multiplied by the number of runs).
-
Add future cables if the spare capacity is expected to be filled later.
-
Add concentrated loads. NEMA practice converts a mid-span point load P into an equivalent uniform load of 2P/L. A 90 kg load on a 3 m span becomes 60 kg/m.
-
Add environmental loads where relevant: wind and ice on covered trays, and wind on large exposed cable bundles.
-
Apply temperature derating. Polyester retains about 90% of its rated strength at about 38 °C and about 78% at about 52 °C under NEMA FG 1 guidance. Divide the design load by the retention factor to get the required rated load.
-
Pick the class or safe working load that meets the required load at your support span, from a tested table.
-
Check width and depth for cable fill plus spare.
-
Choose resin and grades for the chemical and fire environment.
-
Detail supports, splices and expansion in line with the manufacturer’s installation guide.
05Worked example: a substation feeder rack in a refinery
A refinery substation feeds a process unit through a pipe-rack tier. The tray will run outdoors in an ISO 9223 C4 atmosphere, sun-exposed, with supports at 3 m.
-
Cables: 10 runs of a 3.5-core armoured power cable at about 6 kg/m each, plus 6 control cables at about 1.5 kg/m each. Total cable weight: 60 + 9 = 69 kg/m.
-
Future cables: the specification asks for 25% spare capacity, which brings the design cable load to about 86 kg/m.
-
Concentrated load: 90 kg at mid-span, so 2 × 90 ÷ 3 = 60 kg/m equivalent.
-
Design load: 86 + 60 = 146 kg/m.
-
Temperature: the tray may reach about 52 °C in summer sun. In polyester, retention is about 78%, so the required rated load is 146 ÷ 0.78 ≈ 187 kg/m. In vinyl ester, retention at this temperature is typically 90% or more, so the required rated load is about 162 kg/m.
-
Width: the cable bed needs about 520 mm including spare, so select a 600 mm ladder.
-
Selection: a 600 mm ladder with a 150 mm side rail in vinyl ester, whose tested safe working load at 3 m comfortably exceeds 162 kg/m. Alternatively, reduce the span to 2.4 m to use a lighter rail. The cost comparison decides.
The cable weights in this example are indicative. Use the actual values from your cable manufacturer’s data sheets.
06Common ladder-tray problems we see in the field
-
Sag at mid-span from an under-rated side rail or spans longer than the load table allows.
-
Chalky, fibrous surfaces on outdoor trays made without a surface veil or UV inhibitors.
-
Cracked rungs where people have used the tray as a step or rested heavy items on it.
-
Loose splices from missing washers, overtightened bolts that crushed the FRP, or splices placed at mid-span.
-
Rusted hardware from zinc-plated bolts used to save cost.
-
Bowing on long runs where expansion splices were omitted or every support was a fixed clamp.
Each of these is avoidable with the right tray class, grade and installation practice.
07Cleating power cables on FRP ladder trays
Single-core power cables carrying large fault currents push apart violently during a short circuit. Cable cleats hold them in place. Cleats tested to IEC 61914 are specified with a rated short-circuit withstand, and their spacing is set by the prospective fault current and cable diameter.
On FRP ladder trays, three points matter:
-
Fix cleats to rungs, not to side-rail flanges, unless the manufacturer approves it. Rung spacing must match the cleat spacing required by the cleat calculation.
-
Use non-magnetic, corrosion-resistant cleats (for example polymer or SS316) compatible with the environment.
-
Check rung capacity for the cleat load case if the fault level is high. Ask the tray manufacturer to confirm.
Multicore cables are normally secured with UV-stable cable ties or straps at regular intervals on horizontal runs, and more frequently on vertical runs.
08Choosing resin and grade
| Environment | Recommended resin | Comment |
|---|---|---|
| General industrial, indoor or sheltered | Fire-retardant isophthalic polyester | Economical; good weathering with surface veil |
| Coastal, offshore, sun-exposed | Vinyl ester, UV-stabilised | Better heat and chemical resistance |
| Acids, alkalis, chlorine, caustic | Vinyl ester | Polyester is not suitable for strong alkalis |
| High continuous temperature | Vinyl ester; novolac vinyl ester for special cases | Confirm derating data |
| Hazardous areas needing static control | Anti-static (conductive) grade | Per area classification study |
09Ladder vs perforated vs trough trays
| Feature | Ladder | Perforated (ventilated) | Trough / solid bottom |
|---|---|---|---|
| Load and span | Highest | Medium | Medium |
| Cable ventilation | Best | Good | Lowest |
| Support for small cables | Needs closer rungs | Good, continuous base | Best |
| Drainage and dust | Best, self-cleaning | Good | Can collect dust and water unless covered |
| Mechanical protection | Lowest | Medium | Highest, especially with cover |
| Typical cables | Power and control | Instrumentation and control | Instrumentation, data, sensitive circuits |
10Installation tips specific to ladder trays
-
Place splices near supports. Ideally within about a quarter of the span from a support, where bending moment is lower, unless the manufacturer’s tested arrangement allows otherwise.
-
Use the right fittings radius. Bends and risers must suit the minimum bending radius of the largest cable.
-
Seal every site cut with compatible resin.
-
Do not use the tray as a walkway. Rungs are robust, but trays are not platforms.
-
Allow for expansion on long outdoor runs. FRP’s expansion coefficient is about 9 × 10⁻⁶ per °C, lower than steel, but 100 m of tray still moves about 36 mm over a 40 °C swing.
11FGPL FRP ladder cable trays
FGPL pultrudes ladder trays on fully automated lines at its Indore facility, with approximately 60–65% glass content for consistent stiffness. Our ladder trays are approved by ADNOC and Engineers India Limited (EIL), two of the most demanding owners and consultants in the hydrocarbon sector.
-
Widths from 150 mm to 1500 mm, 3 m and 6 m lengths, custom heights and rung spacing.
-
Polyester, vinyl ester and epoxy; fire-retardant and UV-stabilised grades.
-
Complete fittings, covers, splices and SS316 or FRP hardware.
-
Load checks, layouts and documentation from our engineering team.
Explore the range on our FRP ladder cable tray manufacturer page.
Review the full range, then send us your cable schedule for a load check and technical offer.
12Frequently asked questions
What is an FRP ladder cable tray?+
It is a cable support made of two pultruded fibre-reinforced plastic side rails connected by rungs. It carries heavy cable loads over long spans and resists corrosion, while staying electrically non-conductive.
What sizes do FRP ladder cable trays come in?+
FGPL supplies ladder trays from 150 mm to 1500 mm wide in 3 m and 6 m lengths, with side-rail height and rung spacing to suit the cable load and span.
What does a NEMA 12C rating mean?+
It means the tray carries 100 lb/ft (149 kg/m) on a 12 ft (3.66 m) simply supported span, with at least a 1.5 safety factor against failure when tested to NEMA FG 1.
What rung spacing should I use?+
300 mm is common for large power cables. For smaller cables that could sag between rungs, choose closer rung spacing or a perforated tray.
Can FRP ladder trays be used for single-core power cables?+
Yes, with cable cleats rated to IEC 61914 for the prospective short-circuit current, fixed to rungs at the calculated spacing. Confirm rung capacity with the manufacturer for high fault levels.
13References and standards cited
-
NEMA FG 1 — Fiberglass Cable Tray Systems (span/load classes, 1.5 safety factor, temperature reduction guidance).
-
IEC 61537:2023 — Cable tray and cable ladder systems (SWL, 1.7 factor, L/100 deflection).
-
IEC 61914 — Cable cleats for electrical installations.
-
ASTM E84; ASTM D635; UL 94 — fire performance.
Need a ladder tray size confirmed?
Send cable weights, span and environment to FGPL via the contact page or products@fgpl.in for a load-checked recommendation.
This article was prepared by the Applications Engineering team at Fibro Grats Pvt. Ltd. (FGPL), Indore — the team that designs, pultrudes and tests FGPL’s FRP cable tray systems, which are approved by ADNOC and Engineers India Limited (EIL). Data in this article comes from the international standards cited, published resin and industry data, and FGPL’s own engineering practice. Where figures are illustrative, the text says so; for project-specific load tables, test reports and drawings, contact FGPL’s engineering desk.